Representation of analog values
B.3 Representation of analog values in the current output ranges
B.3

Representation of analog values in the current output ranges

The tables below list the decimal and hexadecimal values (codes) of the possible current
output ranges.
Table B- 4
Values
118.5149%
105%
100%
75%
0.003617%
0%
-75%
-100%
-105%
-118.519%
* Outputs positive maximum value or negative minimum value
Table B- 5
Values
118.5149%
105%
100%
75%
0.003617%
0%
-118.519%
* Outputs positive maximum value or negative minimum value
32
Current output range ±20 mA
Dec.
Hex.
32767
7FFF
29031
7167
29030
7166
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-29031
8E99
-29032
8E98
-32768
8000
Current output range 0 to 20 mA
Dec.
Hex.
32767
7FFF
29031
7167
29030
7166
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-32768
8000
Current output range
±20 mA
21 mA
21 mA
20 mA + 723.4 nA
20 mA
15 mA
723.4 nA
0 mA
-723.4 nA
-15 mA
-20 mA
-20 mA + 723.4 nA
-21 mA
-21 mA
Current output range
0 to 20 mA
21 mA
21 mA
20 mA + 723.4 nA
20 mA
15 mA
723.4 nA
0 mA
0 mA
Analog output module AQ 2xI ST (6ES7135-6GB00-0BA1)
Range
Overflow*
Overrange
Nominal range
Underrange
Underflow*
Range
Overflow*
Overrange
Nominal range
Underflow*