Parameters/address space

4.2 Parameters

4.2
Parameters
Parameters of the AQ 2xI ST
The effective range of the configurable parameters depends on the type of configuration.
The following configurations are possible:
● Central operation with an ET 200SP CPU
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation on PROFIBUS DP in an ET 200SP system
When assigning parameters in the user program, use the "WRREC" instruction to transfer
the parameters to the module using the data records; refer to section Parameter assignment
and structure of the parameter data record (Page 26).
The following parameter settings are possible:
Table 4- 2
Configurable parameters and their defaults (GSD file)
Parameters
Diagnostics:
No supply voltage L+
Diagnostics:
Overflow
1
Diagnostics:
Underflow
1
Diagnostics:
Wire break
2
Output type/range
Reaction to CPU STOP
14
Range of values
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Deactivated
Current +/- 20 mA
Current 0 - 20 mA
Current 4 - 20 mA
Turn off
Keep last value
Output substitute value
Default
Parameter
reassignment
in RUN
Disable
Yes
Disable
Yes
Disable
Yes
Disable
Yes
Current 4 -
Yes
20 mA
Turn off
Yes
Analog output module AQ 2xI ST (6ES7135-6GB00-0BA1)
Effective range with configuration
software, e.g. STEP 7
(TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Module
Module
Module
Module
Module
Channel
Channel
Channel
Module
Manual, 12/2015, A5E36104864-AA