C.3

Representation of analog values in the current measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table C- 6
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table C- 7
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
C.3 Representation of analog values in the current measuring ranges
Current measuring range ±20 mA
Current measuring range
hex
±20 mA
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
8000
< -23.52 mA
Current measuring ranges 0 to 20 mA and 4 to 20 mA
Current measuring range
hex
0 to 20 mA
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
ED00
-3.52 mA
8000
<- 3.52 mA
Representation of analog values
4 to 20 mA
>22.81 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
< 1.185 mA
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
47