Representation Of Analog Values In The Current Measuring Ranges - Siemens SIMATIC ET 200SP Manual

Analog input module, ai 2xu/i 2-/4-wire hs 6es7134-6hb00-0da1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Representation of analog values
B.3 Representation of analog values in the current measuring ranges
B.3

Representation of analog values in the current measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table B- 6
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 7
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
* For measurement type "2-wire transducer", negative values are not possible for the range "0 to
20 mA". Therefore, no underrange or underflow exists here.
** For measurement type "2-wire transducer", the behavior described here is supported for overflow
up to max. 35 mA.
48
Current measuring range ±20 mA
Current measuring range
Hex.
±20 mA
7FFF
> 23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
8000
< -23.52 mA
Current measuring ranges 0 to 20 mA and 4 to 20 mA
Current measuring range
Hex.
0 to 20 mA*
7FFF
> 23.52 mA**
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
ED00
-3.52 mA
8000
< -3.52 mA
4 to 20 mA
> 22.81 mA**
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
< 1.185 mA
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Manual, 09/2018, A5E03576060-AF