Representation Of Analog Values In The Current Measuring Ranges - Siemens SIMATIC ET 200MP Manual

Analog input module ai 8xu/i/r/rtd ba
Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

Table C- 6
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
C.3

Representation of analog values in the current measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table C- 7
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Manual, 03/2019, A5E44792324-AA
C.3 Representation of analog values in the current measuring ranges
Voltage measuring range 1 to 5 V
Voltage measuring range
hex
1 to 5 V
7FFF
>5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
< 0.296 V
Current measuring range ±20 mA
Current measuring range
hex
±20 mA
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
8000
< -23.52 mA
Representation of analog values
Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Overflow
Overshoot range
Rated range
Undershoot
range
Underflow
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500

Table of Contents