Phase Current Measurement Cmmxu - ABB Relion 670 Series RES670 Technical Manual

Phasor measurement unit 2.1 ansi
Table of Contents

Advertisement

1MRK 511 365-UUS A
16.1.7.3
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Directionality
If CT grounding parameter is set as described in section
reactive power will be measured always towards the protected object. This is shown in the
following figure 192.
Busbar
52
P
Q
Protected
Object
ANSI05000373 V2 EN
Figure 192:
Internal IED directionality convention for P & Q measurements
Practically, it means that active and reactive power will have positive values when they
flow from the busbar towards the protected object and they will have negative values when
they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side of the
power transformer it might be desirable, from the end client point of view, to have actually
opposite directional convention for active and reactive power measurements. This can be
easily achieved by setting parameter PowAngComp to value of 180.0 degrees. With such
setting the active and reactive power will have positive values when they flow from the
protected object towards the busbar.
Frequency
Frequency is actually not calculated within measurement block. It is simply obtained from
the pre-processing block and then just given out from the measurement block as an output.

Phase current measurement CMMXU

The Phase current measurement (CMMXU) function must be connected to three-phase
current input in the configuration tool to be operable. Currents handled in the function can
be calibrated to get better then class 0.5 measuring accuracy for internal use, on the outputs
and IEC 61850. This is achieved by magnitude and angle compensation at 5, 30 and 100%
IED
ANSI05000373_2_en.vsd
Section 16
Monitoring
"Analog
inputs", active and
515