Application Set-up Examples
6.1.6 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.12 Motor Thermistor
6.1.7 SLC
MG33AQ02
Operating Instructions
Parameters
Function
Setting
Parameter 1-90
[2] Thermistor
Motor Thermal
trip
Protection
Parameter 1-93 T
[1] Analog
hermistor Source
input 53
* = Default Value
Notes/comments:
If only a warning is required,
set parameter 1-90 Motor
Thermal Protection to [1]
Thermistor warning.
D IN 37 is an option.
Parameters
Danfoss A/S © 07/2015 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 6.13 Using SLC to Set a Relay
Notes/comments:
Exceeding the limit in the feedback monitor issues warning
90, Feedback monitor. The SLC monitors warning 90,
Feedback monitor, and if the warning becomes true, relay 1
is triggered.
External equipment indicates if service is required. If the
feedback error goes below the limit again within 5 s, the
frequency converter continues, and the warning
disappears. But relay 1 is still triggered until [Reset] is
pressed on the LCP.
Function
Setting
Parameter 4-30 M
[1] Warning
otor Feedback Loss
Function
Parameter 4-31 M
100 RPM
otor Feedback
Speed Error
Parameter 4-32 M
5 s
otor Feedback Loss
Timeout
Parameter 7-00 Sp
[2] MCB 102
eed PID Feedback
Source
Parameter 17-11 R
1024*
esolution (PPR)
Parameter 13-00 S
[1] On
L Controller Mode
Parameter 13-01 S
[19] Warning
tart Event
Parameter 13-02 S
[44] Reset key
top Event
Parameter 13-10 C
[21] Warning
omparator
no.
Operand
Parameter 13-11 C
[1] ≈*
omparator
Operator
Parameter 13-12 C
90
omparator Value
Parameter 13-51 S
[22]
L Controller Event
Comparator
0
Parameter 13-52 S
[32] Set
L Controller Action
digital out A
low
Parameter 5-40 Fu
[80] SL
nction Relay
digital output
A
*=Default Value
35
6
6
Need help?
Do you have a question about the VLT AutomationDrive FC 301 and is the answer not in the manual?