COMFORT-AIRE B-SVH24SA-1 Service Manual page 37

Century svh series inverter single zone ductless mini-split
Table of Contents

Advertisement

Service Manual - SVH 09/12/18/24 Series
9.3.4 Fan speed has been out of control diagnosis and solution (E3)
Error Code
Malfunction conditions
Possible causes
Troubleshooting:
Power off, then restart the
unit 2 minutes later. Does
unit operate normally?
No
Shut off the power supply.
Can you rotate the fan by hand?
Yes
Check the wiring of
fan motor. OK?
Yes
Measure the voltage for the
fan motor from the main
PCB refer to the
Appendix 1. OK?
Yes
Replace the fan motor. OK?
E3/F5
When indoor fan speed remains too low (300RPM) for certain
time, the unit will stop and the LED will display the failure.
Wiring error
Fan assembly faulty
Fan motor faulty
PCB faulty
Yes
No
No
No
Issue resolved.
Find out the cause and
resolve.
Correct the connections.
Replace the main PCB
No
37