Water top-up

5
Water top-up
14
An automatic water top-up can be carried out in the skimmer or
surge water tank using a level contact.
Please note that the drinking water connection may not be con‐
nected to the pool circuit. See the corresponding DVGW (German
Gas and Water Association) or FIGAWA (German Federal Associ‐
ation of Gas and Water Companies) regulations or your own
national regulations.
1.
Connect the single-stage level switch in the A module to ter‐
[K1 7/8]
minal
2.
In configuration on the A module set terminal
3.
Thereafter terminal
4.
If the [TIME] [water level] is set to [0 s], then after
10 seconds constantly at the minimum level, the
Level evaluation unit reacts by opening the water
supply solenoid valve. After 10 seconds con‐
stantly at the maximum liquid level, the solenoid
valve for the water supply is closed. If a [TIME]
[water level] of for example [30 s] is set, then for
this 30 seconds water continues to be supplied,
so that the maximum liquid level is reached after
this time.
[TIME] [water level] can be set from 0 ... 480 seconds in
The
steps
5.
To actuate a solenoid valve with 230 V, it is necessary to
connect this solenoid valve to the PCB of the P module on
terminal 2 (with one circulation) or terminal 1 (with two circu‐
lations)
6.
Program the configuration menu of this relay using the func‐
tion
[Water top-up]
ð
If water is topped up for longer than 180
minutes the controller enters fault mode and
stops the topping up.
This this function is active
7.
If the control time has elapsed and the controller is in fault
mode, then you must press the
module configuration menu under service
water top-up in operating mode
[K1] can be activated as a water level
[F3] key for [Reset] in the A
[F2] . This restarts
[AUTO]
[R1] to 'free'