Vega VEGAPULS 66 Quick Setup Manual

Foundation fieldbus radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 66:

Advertisement

Quick Links

Quick setup guide

Radar sensor for continuous level
measurement of liquids
VEGAPULS 66
Foundation Fieldbus
Document ID: 47141

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VEGAPULS 66 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vega VEGAPULS 66

  • Page 1: Quick Setup Guide

    Quick setup guide Radar sensor for continuous level measurement of liquids VEGAPULS 66 Foundation Fieldbus Document ID: 47141...
  • Page 2: Table Of Contents

    Operating Instructions Manual as well as the Safety Manual that comes with instruments with SIL qualification. These manuals are available in the download area of "www.vega.com". Operating instructions VEGAPULS 66 - Foundation Fieldbus: Document-ID 36522 Editing status of the quick setup guide: 2018-02-16 VEGAPULS 66 • Foundation Fieldbus...
  • Page 3: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use VEGAPULS 66 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
  • Page 4: Eu Conformity

    It is hence approved for use inside closed vessels in countries of the Use is also approved in EFTA countries, provided the respective standards have been implemented. For operation inside of closed vessels, points a to f in annex E of EN 302372 must be fulfilled. Radio license for USA This approval is only valid for USA. Hence the following text is only available in the English language. VEGAPULS 66 • Foundation Fieldbus...
  • Page 5: Environmental Instructions

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGAPULS 66 • Foundation Fieldbus...
  • Page 6: Product Description

    Test certificate (PDF) - optional Go to "www.vega.com", "Instrument search (serial number)". Enter the serial number. Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
  • Page 7 2 Product description This operating instructions manual applies to the following instrument Scope of this operating instructions manual versions: • Hardware from 2.1.1 • Software from 4.5.0 VEGAPULS 66 • Foundation Fieldbus...
  • Page 8: Mounting

    > 10 mm into the vessel > 500 mm (19.69") Fig. 2: Distance of the antenna to the vessel wall/vessel ceiling 2. Note min. socket diameter depending on the socket length For further information see chapter "Mounting". VEGAPULS 66 • Foundation Fieldbus...
  • Page 9: Connecting To The Bus System

    When the screwdriver is released, the terminal closes again. You can find further information on the max. wire cross-section under "Technical data - Electromechanical data". 7. Check the hold of the wires in the terminals by lightly pulling on them VEGAPULS 66 • Foundation Fieldbus...
  • Page 10: Wiring Plan, Single Chamber Housing

    Voltage supply, signal output For display and adjustment module or interface adapter For external display and adjustment unit Ground terminal for connection of the cable screen Information: Parallel use of an external display and adjustment unit and a display and adjustment module in the terminal compartment is not supported. VEGAPULS 66 • Foundation Fieldbus...
  • Page 11: Set Up With The Display And Adjustment Module

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 6: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing VEGAPULS 66 • Foundation Fieldbus...
  • Page 12: Parameter Adjustment

    2. In the menu item "Medium"you select the medium of your applica- tion, for example "Aqueous solution". 3. Select in the menu item "Application" the vessel, the application and the vessel form, for example, storage tank. 4. Carry out the adjustment in the menu items "Min. adjustment" and "Max. adjustment". VEGAPULS 66 • Foundation Fieldbus...
  • Page 13 With the adjustment software PACTware and a PC, a high resolution echo curve can be displayed and used to recognize signal changes during operation. In addition, the echo curve of setup can be dis- played in the echo curve window and compared with the current echo curve. VEGAPULS 66 • Foundation Fieldbus...
  • Page 14 Delete: An already created false signal suppression will be com- pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel. Extend: is used to extend an already created false signal suppres- sion. This is useful if a false signal suppression was carried out with VEGAPULS 66 • Foundation Fieldbus...
  • Page 15: Menu Overview

    20.5 mA Released Lock adjustment Display Menu item Default setting Language Order-specific Displayed value Filling height in % Switched on Backlight Diagnostics Menu item Parameter Default setting Sensor status Peak value Distance Electronics tem- Temperature perature Measurement re- liability VEGAPULS 66 • Foundation Fieldbus...
  • Page 16 Actual date/Actual time Reset HART mode Address 0 Copy instrument set- tings Info Menu item Parameter Device name VEGAPULS 6. Instrument version Hardware and software version Date of manufacture Date Device ID Instrument features Order-specific characteristics VEGAPULS 66 • Foundation Fieldbus...
  • Page 17: Supplement

    13.5 … 32 V DC Ʋ Ex-ia instrument - Power supply 13.5 … 17.5 V DC FISCO model Ʋ Ex-ia instrument - Power supply 13.5 … 24 V DC ENTITY model Ʋ Ex-d-ia instrument No lighting possible (integrated ia barrier) Power supply by/max. number of sensors Ʋ Fieldbus max. 32 (max. 10 with Ex) VEGAPULS 66 • Foundation Fieldbus...
  • Page 18 Notes VEGAPULS 66 • Foundation Fieldbus...
  • Page 19 Notes VEGAPULS 66 • Foundation Fieldbus...
  • Page 20: Information

    Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2018 VEGA Grieshaber KG Phone +49 7836 50-0 Am Hohenstein 113...