Parameter window
A: Function
Commissioning
In this parameter window, you determine the behaviour of the output and
can enable different functions, where further parameters windows become
available.
Monitoring of the controller
Options:
no
yes
no: The parameter window A: Monitoring for output A is not enabled.
yes: The parameter window A: Monitoring for output A is enabled. There
the communication object RTR fault can be enabled for monitoring. Thus
a failure of the room thermostat can be detected, the output changed to
fault mode and a parameterised valve position can be set.
Enable function "forced operation"
Options:
no
yes
With forced operation, the output can assume a determined position, e.g. for
inspection purposes.
no: The parameter window A: Forced Operation for output A is not
enabled.
yes: The parameter window A: Forced Operation for output A as well as
the communication object Forced operation are enabled.
SA/S | 2CDC 505 056 D0207 117