Parameter Window A: Logic - ABB SA/S 12.16.6.1 Product Manual

Switch actuators
Hide thumbs Also See for SA/S 12.16.6.1:
Table of Contents

Advertisement

®
ABB i-bus
KNX
3.2.3.1.4
Parameter window
A: Logic
84 2CDC 505 056 D0207 | SA/S
Commissioning
In this parameter window, all settings for the function Logic are undertaken.
This parameter is visible if in parameter window
parameter Function Logic has been enabled.
The function Enable function "logic" provides up to two logic objects for each
output, which can be logically linked with the Switch communication object.
The logic is always re-calculated when an object value is received. Hereby,
the communication object Logical connection 1 is first of all evaluated with
the communication object Switch. The result is then logically linked with the
communication object Logical connection 2.
Explanations of the logic function can be found at
Connection/Logic, page 145. Please also observe the
139, where the priorities become evident.
Logical connection 1 active
Options:
inactive
active
With these parameters, the communication object Logical connection 1 is
enabled.
active: The following parameters appear:
Function, page 64, the
A:
Function
chart, page
Function

Advertisement