Introduction; Fc500 Fire Contro Panel; Accessory Items; Description - FireClass 500 Installer Manual

Addressable fire control panels
Table of Contents

Advertisement

FC500 Fire Contro Panel

In this manual we will use the term FC500 control panel
to indicate the common features of Fire control panel.
Otherwise we will use the specific terms.
FC500 Fire control panel is avalaible in the following
models:
Ø FC510 - Analogue addressable Fire Control Panel
with one not expandable Loop and with Switching
Power supply 5,5 A;
Ø FC520 - Analogue addressable Fire Control Panel
with two not expandable Loops and with Switching
Power supply 5,5 A;
+
The components of these Control panels operate
as intended when the external ambient conditions
comply with the requirements of class EN
60721-3-3:1995.
The Loops of FC500 control panel provide the follo-
wing features:
Ø max 250 analogue devices.
Ø The conventional line of the FC500 contro Panel can
support up to 30 devices.
In any case, FC500 Fire control panel cannot sup-
port more than 2000 devices (500 devices for every
couple of Loop) (up to 2000 m (Loop) with shielded
cable 2x2.5).
The FC500 control panel must be powered by
BAQ140T24 (27,6 V - 5,5 A ) switching power supply.
Moreover all FC500 models provide housing for an LCD
module with 40 characters for line and 4 lines backlit,
which provides written information regarding the
system status and for programming the control panel.
n Accessory Items
FC500REP This Repeater panel is intended for con-
nection (via 4 wires) to FC500 Control panels. It provi-
des all the visual and audible warnings generated by
the Control panel and allows end-users to manage the
system from a remote location (up to 1000 m, with dou-
ble twist shielded cable).
The FC500 "Master" Control panels can support up to
(8) eight FC500REP Repeater panels.
FC500 Slave The FC500 "Master" Control panels can
support up to (7) seven FC500 Slave Control panels.
These Control Panels can be used to expand the
FC500 system, in modular way.
Software FireClass500 Console This user-friendly
software application (Windows) offers a quick and easy
way to program the Control panel and provides event
log functions.

Description

n Input
250 devices max every Loop
30 devices max on the conventional line
n Outputs
This section describes how the Control panel outputs
operate.
Supervised outputs The Control panel will be able to
detect and signal short-circuits and power supply inter-
ruptions on this type of output.
Bypassable(Disabled) outputs The user will be able
to disable (by means of the respective key) this type of
output.
Silenceable outputs The user will be able to stop (via
the Silence key) this type of output.
The outputs can be silenced for an indefinite period (du-
ring Day Mode), or for the programmed Silence Time
(during Night Mode).

INTRODUCTION

INTRODUCTION
5