Contents Introduction ....................4 Symbols used ............4 Abbreviations ............4 General ..............4 1.3.1 Manufacturer's liability ..........4 1.3.2 Installer's liability .............5 Certifications ............5 Safety instructions and recommendations ..........6 Recommendations ..........6 Technical description ................7 Description of the keys ........7 Description of the display ........8 3.2.1 Key functions ............8 3.2.2...
Page 3
Contents 4.4.7 Pool connection .............23 4.4.8 Connecting a mixed tank ........25 4.4.9 Connecting the options .........25 4.4.10 Connection in cascade ..........27 Operating the appliance ................30 Powering up for the first time ......30 Access to the various browsing levels .....30 5.2.1 User level ..............30 5.2.2 Installer level ............31...
Page 4
Failure history .............59 Parameter and input/output check (mode tests) ..............59 12/04/2011 - 300025649-001-B...
iSense Pro DIN - AD280 1. Introduction Introduction Symbols used In these instructions, various danger levels are employed to draw the user's attention to particular information. In so doing, we wish to safeguard the user's safety, obviate hazards and guarantee correct operation of the appliance.
1. Introduction iSense Pro DIN - AD280 In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice. Our liability as the manufacturer may not be invoked in the following cases: 4 Failure to abide by the instructions on using the appliance.
iSense Pro DIN - AD280 2. Safety instructions and recommendations Safety instructions and recommendations Recommendations WARNING Only qualified professionals are authorised to work on the appliance and the instalation. The appliance should be on Summer or Antrifreeze mode rather than switched off to guarantee the following functions: 4 Anti blocking of pumps.
3. Technical description iSense Pro DIN - AD280 Technical description Description of the keys AUTO Temperature setting key (heating, DHW, swimming pool) Operating mode selection key DHW override key Key to access the parameters reserved for the installer Keys on which the function varies as and when selections are made Rotary setting button: Turn the rotary button to scroll through the menus or...
iSense Pro DIN - AD280 3. Technical description Description of the display 3.2.1. Key functions Access to the various menus > Used to scroll through the menus Used to scroll through the parameters The symbol is displayed when help is available Used to display the curve of the parameter selected <...
3. Technical description iSense Pro DIN - AD280 Operation in automatic mode according to the timer AUTO programme Comfort mode: The symbol is displayed when a DAY override (comfort) is activated Flashing symbol: Temporary override < AUTO Steady symbol: Permanent override Reduced mode: The symbol is displayed when a NIGHT override (reduced) is activated Flashing symbol: Temporary override...
Page 11
iSense Pro DIN - AD280 3. Technical description Outside sensor Outlet sensor circuit B+C Domestic hot water sensor System sensor -20 °C 2392 ¨ 32014 ¨ 0 °C -16 °C 2088 ¨ 19691 ¨ 10 °C -12 °C 1811 ¨ 12474 ¨...
4. Installation iSense Pro DIN - AD280 Installation Package list The delivery includes: 4 The iSense Pro DIN module 4 Electrical harness 4 Extension cable marked K1 (For connecting a GAS 210 ECO PRO boiler) 4 Outside sensor 4 Flow sensor (x2) 4 DHW sensor 4 Earth terminal block + 2 screws 4 Installation and Service Manual...
iSense Pro DIN - AD280 4. Installation Recommended position Possible position Inhabited height controlled by the sensor Inhabited area controlled by the sensor 8800N001-C Positions to be avoided: 4 masked by a building element (balcony, roof, etc.) 4 close to a disruptive heat source (sun, chimney, ventilation grid, etc.) 8800N002-C 4.2.2.
4. Installation iSense Pro DIN - AD280 Mounting and connecting the module 4.3.1. Boiler GAS 210 ECO PRO C003311-B C003312-B CAUTION Step 3: Connect the extension cable K1 between connectors A and Z. 12/04/2011 - 300025649-001-B...
iSense Pro DIN - AD280 4. Installation C003319-B C003320-B Electrical connections 4.4.1. Recommendations WARNING Only qualified professionnals may carry out electrical connections, always with the power off. The boiler is entirely pre-wired. Do not modify the connections inside the control panel. Earth the appliance before making any electrical connections.
4. Installation iSense Pro DIN - AD280 4.4.2. Connecting a heating circuit S Syst. 0-10V 0V B A N L N L N L N L C002815-A 3 way valve circuit B Heating pump circuit B Outlet sensor circuit B Heating circuit B Outside sensor Boiler...
iSense Pro DIN - AD280 4. Installation 4.4.3. Connecting a heating circuit and a domestic hot water tank S Syst. 0-10V 0V B A N L N L N L N L C002816-A 3 way valve circuit B Heating pump circuit B Outlet sensor circuit B Heating circuit B Outside sensor...
4. Installation iSense Pro DIN - AD280 4.4.4. Connecting two circuits and a domestic hot water tank S Syst. 0-10V 0V B A N L N L N L N L C002817-A 3 way valve circuit B Heating pump circuit B Outlet sensor circuit B Heating circuit B Outside sensor...
iSense Pro DIN - AD280 4. Installation Earth the various pumps and 3-way valves. Settings to be made for this type of installation Parameters Access Settings to be made See chapter ¼ "Displaying the parameters in extended INSTALLATION Installer level EXTENDED #SYSTEM menu mode", page 33...
4. Installation iSense Pro DIN - AD280 Heating pump circuit C Heating circuit C Earth the various pumps and 3-way valves. Settings to be made for this type of installation Parameters Access Settings to be made See chapter ¼ "Displaying the parameters Installer level INSTALLATION EXTENDED...
Page 23
iSense Pro DIN - AD280 4. Installation S Syst. 0-10V 0V B A N L N L N L N L C002818-B This type of installation only works if the boiler incorporates a boiler pump managed by the boiler regulator. Boiler regulator Connect the heating pump (Circuit B).
4. Installation iSense Pro DIN - AD280 The DHW part is maintained at the DHW set point by the boiler. The heating zone is maintained at the set temperature calculated according to the outside temperature. The zone is reheated when the heating buffer temperature sensor T falls -6°C below the calculated set temperature.
Page 25
iSense Pro DIN - AD280 4. Installation Settings to be made for this type of installation Parameters Access Settings to be made See chapter ¼ "Displaying the Installer level INSTALLATION EXTENDED #SYSTEM menu parameters in extended mode", page 33 ¼ "Professional settings", Installer level Set the value of MAX.
4. Installation iSense Pro DIN - AD280 n Hourly programming of the secondary circuit pump The secondary pump operates during programme B comfort periods in summer and winter alike. n Stopping To prepare your pool for winter, consult your pool specialist. 4.4.8.
Page 27
iSense Pro DIN - AD280 4. Installation S Syst. 0-10V CDI CDR 0V B A N L N L N L N L MODE TELCOM 2 MODE C002821-C Connect the load pump of the second tank. Second domestic hot water tank. Connect the DHW sensor of the second tank.
4. Installation iSense Pro DIN - AD280 4.4.10. Connection in cascade n DHW tank after the mixing tank C002822-A Master boiler Secondary boiler Secondary boiler D.H.W. load pump DHW sensor Cable BUS Low loss header Cascade outlet sensor Connect the sensor to the terminal block E.SYST on the master boiler.
Page 29
iSense Pro DIN - AD280 4. Installation Settings to be made for this type of installation: Follower boilers Parameters Access Settings to be made See chapter ¼ "Displaying the parameters in extended Installer level INSTALLATION EXTENDED #SYSTEM menu mode", page 33 ¼...
Page 30
4. Installation iSense Pro DIN - AD280 Outside sensor Settings to be made for this type of installation: Master boiler Parameters Access Settings to be made See chapter ¼ "Displaying the parameters in extended Installer level INSTALLATION EXTENDED #SYSTEM menu mode", page 33 ¼...
iSense Pro DIN - AD280 5. Operating the appliance Operating the appliance Powering up for the first time The first time the boiler is powered up, the #LANGUAGE menu is displayed. LANGUE FRANCAIS 1. Select the desired language by turning the rotary button. Français - Deutsch - English - Italiano - Espanol - Nederlands - Pycck...
5. Operating the appliance iSense Pro DIN - AD280 5.2.2. Installer level The information and settings in the Installer level can be accessed by experienced people. 1. Press key - for around 5 seconds. Before the Installer level is displayed, the #EMISSION SUNDAY 11:45 MEASUREMENTS menu will be displayed.
iSense Pro DIN - AD280 5. Operating the appliance 3. To select the desired parameter, turn the rotary button. 4. To modify the parameter, press the rotary button. CURRENT PROG.B To go back to the previous display, press the key j . CURRENT PROG.C <...
5. Operating the appliance iSense Pro DIN - AD280 User level - #MEASURES menu Parameter Description Unit Water temperature in the DHW tank °C WATER TEMP. Water temperature in the storage tank °C STOR.TANK.TEMP Water temperature of the swimming pool on circuit B °C SWIMMING P.T.B Water temperature of the swimming pool on circuit C...
iSense Pro DIN - AD280 5. Operating the appliance Regardless of what is done to the keys, the regulator switches back to CLASSIC mode after 30 minutes. 5.5.2. Setting the parameters specific to the installation 1. Access the installer level: Press key - for around 5 seconds. 2.
Page 36
5. Operating the appliance iSense Pro DIN - AD280 Installer level - #SYSTEM menu Parameter Adjustment range Description Factory setting Customer setting See table below. CLOSE CLOSE CT.TEL OPEN Start anti-freeze in boiler command (1)(2) ANTIFR ANTIFR I.TEL: ON or OFF contact: I.TEL: can be used as an 0/1 B antifreeze activation inlet on circuit B ON or OFF contact: I.TEL: can be used as an...
iSense Pro DIN - AD280 5. Operating the appliance 5.5.3. Naming the circuits and generators 1. Access the installer level: Press key - for around 5 seconds. 2. Select the menu #NAMES OF THE CIRCUITS. SUNDAY 11:45 Turn the rotary button to scroll through the menus or TEMP.: 68°...
5. Operating the appliance iSense Pro DIN - AD280 5.5.4. Setting the heating curve If an outside temperature sensor is connected, it is possible to adapt the heating curve. 1. Access the installer level: Press key - for around 5 seconds. 2.
iSense Pro DIN - AD280 5. Operating the appliance Maximum temperature of the circuit C° Water temperature in the circuit for an outside temperature of 0°C DAY set point on the circuit Outside temperature for which the maximum water temperature in the circuit is reached Value of the heating curve This value corresponds to the parameter HEAT.CURV.
5. Operating the appliance iSense Pro DIN - AD280 5.6.1. Language selection 1. Access the installer level: Press key - for around 5 seconds. 2. Select the menu #LANGUAGE. SUNDAY 11:45 Turn the rotary button to scroll through the menus or TEMP.: 68°...
iSense Pro DIN - AD280 5. Operating the appliance User level - #SETTING menu Parameter Adjustment range Description Factory setting Customer setting 15 to 30 °C Used to set the outside temperature 22 °C SUM/WIN above which heating will be shut down. The heating pumps are shut down.
Page 42
5. Operating the appliance iSense Pro DIN - AD280 Installer level - #SECONDARY LIMITS menu Parameter Adjustment range Description Factory setting 20 to 95 °C Maximum temperature (Circuit B) 50 °C MAX.CIRC.B ¼ "MAX.CIRC...", page 43 20 to 95 °C Maximum temperature (Circuit C) 50 °C MAX.CIRC.C...
Page 43
iSense Pro DIN - AD280 5. Operating the appliance Installer level - #SECONDARY INSTAL.P menu Parameter Adjustment range Description Factory Customer setting setting The lower temperature is maintained DEC. DEC. NIGHT (Night mode) ¼ "NIGHT", page 44 The boiler is stopped (Night mode) STOP ¼...
Page 44
5. Operating the appliance iSense Pro DIN - AD280 Installer level - #SECONDARY INSTAL.P menu Parameter Adjustment range Description Factory Customer setting setting The anti legionella function acts to prevent LEG PROTEC the development of legionella in the dhw tank, these bacteria are responsible for legionellosis.
Page 45
iSense Pro DIN - AD280 5. Operating the appliance When floor drying is active on a circuit, all other circuits (e.g. DHW) are shut down. The use of this function is only possible on circuits B and C. STOP DRYING TEMP START DRYING TEMP Today NB DAYS DRYING...
5. Operating the appliance iSense Pro DIN - AD280 For circuits with a room sensor: 4 When the room temperature is lower than the room sensor set point: The reduced temperature is maintained during reduced periods. The circuit pump operates constantly. 4 When the room temperature is higher than the room sensor set point: Heating is shut down during reduced periods.
Page 47
iSense Pro DIN - AD280 5. Operating the appliance Installer level - Menu #NETWORK Parameter Adjustment range Description Factory setting Customer setting ON / NO ON: System in cascade CASCADE: ON / NO Configure this control system as MASTER CONTROLLER master on the bus Specific menu: Enlist generators or SYSTEM NETWORK...
Page 48
5. Operating the appliance iSense Pro DIN - AD280 3. To add a slave appliance to the network, select ADD GENE MANU. NB.NETWORK ELEMENTS ADD SLAVE ERASE NETWORK < AUTO C002410-C-04 4. The screen displayed allows you to choose numbers for the slave boilers to be added to the network.
Page 49
iSense Pro DIN - AD280 5. Operating the appliance 2. Choose a number to allocate to the scenario by turning the rotary button, up to 4 scenarios can be saved. To confirm, press the rotary button. SCENARIO "Please choose the scenario to define" <...
Page 50
5. Operating the appliance iSense Pro DIN - AD280 2. Choose the device to be removed by turning the rotary button and pressing to confirm. MASTER CONTROLER "Select the InOne device to remove" < AUTO C002420-C-04 n Controlling the boiler from an IOBL Scenario Switch It is possible to control the boiler from a scenario switch (the boiler is then considered a slave boiler).
Page 51
iSense Pro DIN - AD280 5. Operating the appliance 230V LEARN ? "An external devicetries to connect, do you want to authorize it?" 230V < AUTO C002422-B-04 2. Press the LEARN key and the control key used to pilot the scenario.
Page 52
5. Operating the appliance iSense Pro DIN - AD280 5. Choose the desired scenario by turning the rotary button and then confirm. HOLIDAYS FUNCTION : "Function of the scenario" Scenarios available Description Heating according to the time programme AUTO < AUTO Comfort mode Reduced mode...
iSense Pro DIN - AD280 5. Operating the appliance 5.6.5. Return to the factory settings To reset the appliance, proceed as follows: 1. Press key C , > and j simultaneously for 4 seconds. The menu 4" #RESET is displayed. 2.
6. Switching off the appliance iSense Pro DIN - AD280 Switching off the appliance Installation shutdown If the central heating system is not used for a long period, we recommend switching the boiler off. 4 Switch the On/Off switch on Off. 4 Isolate the gas supply.
iSense Pro DIN - AD280 7. Troubleshooting Troubleshooting Installer's contact details To display the installer's telephone number when an error is displayed, proceed as follows: 1. Access the "After Sales" level: Hold key - down until #PARAMETERS is displayed. 2. Select the menu #SUPPORT. SUNDAY 11:45 TEMP.: _ _ _ _ Turn the rotary button to scroll through the menus or...
7. Troubleshooting iSense Pro DIN - AD280 Message history The menu (#MESSAGE HISTORIC) is used to consult the last 10 messages displayed by the control panel. 1. Access the "After Sales" level: Hold down the - key until #PARAMETERS is displayed. 2.
Page 57
iSense Pro DIN - AD280 7. Troubleshooting Code Faults Description Checking / solution Circuit B flow sensor fault Bad connection OUTL S.B FAIL. Circuit C flow sensor fault OUTL S.C FAIL. ¼ See Check whether the sensor is connected: Remarks: chapter: "Deletion of sensors from the memory The circuit pump is running.
Page 58
7. Troubleshooting iSense Pro DIN - AD280 Code Faults Description Checking / solution Break in communication between the Bad connection MC COM.FAIL iSense Pro DIN module and the boiler Check the link and the connectors radio module Boiler module failure Change the boiler module Storage tank sensor fault Bad connection...
iSense Pro DIN - AD280 7. Troubleshooting Code Faults Description Checking / solution The IOBL function is no longer active Problem on the iSense Pro DIN module COM.IOBL FAIL. If the IOBL function is not used, deactivate the IOBL function in the menu #CONFIGURATION If the IOBL function is used, change the iSense Pro DIN module and re-pair the peripherals (IOBL 3WV module, Interscenario switch)
Page 60
7. Troubleshooting iSense Pro DIN - AD280 Failure history The menu #DEFAULT HISTORIC is used to consult the last 10 faults displayed by the control panel. 1. Access the "After Sales" level: Hold down the - key until #PARAMETERS is displayed. 2.
Page 61
iSense Pro DIN - AD280 7. Troubleshooting After Sales level - #PARAMETERS menu Parameter Description Master boiler active PERMUT Number of boilers requesting heating STAGE Number of boilers recognised in the cascade NB.CASC.: Number of DIEMATIC VM control systems recognised in the cascade NB.
Page 62
7. Troubleshooting iSense Pro DIN - AD280 After Sales level - #TEST INPUTS menu Parameter Status OK Description Status of the telephone inlet 0 / 1 PHONE REM. Presence of an error FAILURE ON / NO Presence of a remote control B R.CTRL B No remote control B Presence of a remote control C...
Page 63
iSense Pro DIN - AD280 7. Troubleshooting 12/04/2011 - 300025649-001-B...
Need help?
Do you have a question about the iSense Pro DIN AD280 and is the answer not in the manual?
Questions and answers