iSense Pro DIN - AD280
Installer level - Menu #NETWORK
Parameter
CASCADE:
MASTER CONTROLLER
(2)
(3)
SYSTEM NETWORK
(3)
FUNCT
(4)
PARALLEL CASC.
(2)
TIMER GENE P. CASC
(2)
INTER STAGE TIMER
(5)
SLAVE NUMBER
3WW PLC
InOne SCENARIO
REMOVE DEVICE
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
(2) The parameter is only displayed if CASCADE: is set to ON
(3) The parameter is only displayed if MASTER CONTROLLER is set to ON
(4) The parameter is only displayed if FUNCT is set to PARALLEL
(5) The parameter is only displayed if MASTER CONTROLLER is set to OFF
0
2
4
6
8
10
12
14
CASCADE
MASTER CONTROLER
E
1
SYSTEM NETWORK
2
FUNCT
1
D
2
INTER STAGE TIMER
#
F
!

% $
AUTO
J
I
STD
12/04/2011 - 300025649-001-B
(1)
Adjustment range Description
ON / NO
ON: System in cascade
ON / NO
Configure this control system as
master on the bus
Specific menu: Enlist generators or
VMs in cascade mode (See following
chapter: "Connecting appliances in
cascade")
Operation in cascade: Successive
CLASSIC
triggering of the various boilers in the
cascade according to requirements
Functioning in parallel cascade: If the
PARALLEL
outside temperature is lower than the
value PARALLEL CASC., all of the
boilers are started up at the same time
-10 to 20 °C
Outside temperature triggering all
stages in parallel mode
0 to 30 min
Minimum duration of post-operation of
the generator pump
1 to 30 min
Time delay for starting up or shutting
down generators.
2 to 10
Set the network address of the
secondary generator
Specific menu (Not used)
Specific menu: Configure the InOne
scenarios to be managed by the SCU
PCB (See following chapter:
"Configuring the scenarios")
Specific menu: see below
16
18
20
22
24
ON
ON
TRADITIONAL
4'
9
<
C002409-C-04
n Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VMs as slaves. Proceed as follows:
1. Set CASCADE: to ON by pressing the rotary button and then
turning and pressing it again to confirm.
2. Select SYSTEM NETWORK and press the rotary button to go to
the specific menu.
5. Operating the appliance
Factory setting Customer setting
NO
ON
CLASSIC
10 °C
0 mn
4 mn
2
46