REMEHA iSense Pro DIN AD280 Installation And Service Manual page 42

Hide thumbs Also See for iSense Pro DIN AD280:
Table of Contents

Advertisement

5. Operating the appliance
Installer level - #SECONDARY LIMITS menu
Parameter
Adjustment range Description
20 to 95 °C
MAX.CIRC.B
20 to 95 °C
MAX.CIRC.C
OFF, -8 to +10 °C
OUT.ANTIFREEZE
(1)(2)
OFF, 20 to 90 °C
HCZP D B
OFF, 20 to 90 °C
(1)(2)
HCZP N B
OFF, 20 to 90 °C
(1)(2)
HCZP D C
(1)(2)
OFF, 20 to 90 °C
HCZP N C
50 to 90 °C
(1)
PRIM.TEMP.DHW
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f.
Installer level - #SECONDARY INSTAL.P menu
Parameter
Adjustment range
0 (10 hours) to 10
(1)
BUILD. INERTIA
(50 hours)
0 to 4
(2)
CIRC.CURVE B
0 to 10
(1)
ROOM INFL. B
0 to 4
(2)
CIRC.CURVE C
(1)
0 to 10
ROOM INFL. C
SCREED DRYING
NO, B, C, B+C
20 to 50 °C
START DRYING
(3)
TEMP
20 to 50 °C
STOP DRYING
(3)
TEMP
(3)
0 to 99
NB DAYS DRYING
(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f
(3) The parameter is only displayed if SCREED DRYING is other than OFF
(4) The parameter is only displayed if IN 0-10V is set to ON.
(5) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
41
Maximum temperature (Circuit B)
¼ "MAX.CIRC...", page 43
Maximum temperature (Circuit C)
¼ "MAX.CIRC...", page 43
Outside temperature at which the installation's antifreeze
protection is activated.
Below this temperature the pumps are permanently on and the
minimum temperatures for each circuit are respected.
When NIGHT : STOP is set, the reduced temperature is
maintained in each circuit (#SECONDARY INSTAL.P menu).
OFF: Antifreeze protection is not activated
Curve base temperature in Daytime mode (Circuit B)
Curve base temperature in Nighttime mode (Circuit B)
Curve base temperature in Daytime mode (Circuit C)
Curve base temperature in Nighttime mode (Circuit C)
Boiler temperature setting if producing domestic hot water
Description
Characterisation of building's inertia:
0 for a building with low thermal inertia.
3 for a building with normal thermal inertia.
10 for a building with high thermal inertia.
Modification of the factory setting is
only useful in exceptional cases.
Heating curve of the circuit B
¼ "CIRC. CURVE ...", page 43
Influence of room sensor B
¼ "ROOM S.INFL", page 44
Heating curve of the circuit C
¼ "CIRC. CURVE ...", page 43
Influence of room sensor C
¼ "ROOM S.INFL", page 44
Drying the floor
¼ "SCREED DRYING", page
43
Screed drying start temperature
Screed drying stop temperature
iSense Pro DIN - AD280
Factory setting
50 °C
50 °C
+3 °C
OFF
OFF
OFF
OFF
80 °C
Factory
Customer
setting
setting
3 (22 hours)
0.7
3
0.7
3
NO
20 °C
20 °C
0
12/04/2011 - 300025649-001-B