Version With Mechanical Override - Samson 3274 Mounting And Operating Instructions

Electrohydraulic
Table of Contents

Advertisement

Manual operation of actuator
6.2 Version with mechanical
override
1. Press the black release button at the front
of the housing.
2. Insert a hexagon wrench (width across
flats 24) into the shaft end protruding
from the housing to move the rack-and-
pinion gear until the require actuator
stem position has been reached.
As soon as the button is released, the actua-
tor reacts again to the controller signal.
If the valve is to remain in the manually de-
fined position, disconnect the isolating termi-
nal 81 as described in section 6.1.
100%
Actuator stem
retracted
Travel
Actuator stem
extended
0%
4
100%
Split-range operation
0%
Fig. 8: Characteristics
20
< >
>>
20 mA
Input signal
< >
>>
4
12
20 mA
Dead band
EB 8340 EN