Calibration for direction of action increasing/decreasing (<>):
14. Set slider switch SW2 to ON.
15. Turn "Zero in" adjuster clockwise as far as it will go:
Zero
in
60
40
80
20
100
%
0
16. Set the input signal to 0 V or 0 mA.
17. Slowly turn the "Zero in" adjuster clockwise until the LED turns off. Turn it slightly further
until the LED lights up again.
18. Connect isolating terminal 81:
Red marking pin
Release button
7.1.5

Using the positioner as a position transmitter

The positioner can be used as a position transmitter with three-step control.
1. Disconnect the wires leading to the terminals aL and eL.
Î Make sure that the disconnected wires are properly insulated (e.g. by using installation
clamps).
2. Wire the conductors of the external three-step control signal (controller) to the terminals
aL, eL, and 81 (the terminals 11, 12, and 13 as well as the priority circuit at terminals 82
and 83 do not function as a result).
EB 8340 EN
Span
Span
out
in
on
off
1
2
3
Operation
4
25