7 Operation

After connecting the supply voltage, the ac-
tuator is ready for use.

7.1 Three-step mode

In three-step mode, the actuator stem is
moved in the corresponding direction by ap-
plying a signal to the terminal eL or aL (see
Fig. 7-1).
Actuators with fail-safe action additionally
require a constant supply voltage (see the
'Installation' section).
Fig. 7-1: Three-step control
EB 8331-3 EN
eL
aL

7.2 Mechanical override

To operate the manual override, place a
4 mm hex wrench on the red actuator shaft
located at the side of the housing (see
Fig. 7-2). Turn the hex wrench clockwise to
move the actuator in 'aL' direction and
counterclockwise to move it in the 'eL'
direction (see Fig. 7-1). The hex wrench is
included in the scope of delivery. It is
attached to the bottom of the housing.
Fig. 7-2: Actuating shaft for manual override
Note
Manual override is only possible in actuators
with fail-safe action when the supply voltage
(terminals L and N) is connected.