Initial Start-Up - Daikin EHS157034 Operating Instructions Manual

Hide thumbs Also See for EHS157034:
Table of Contents

Advertisement

4
x

Initial start-up

4
Initial start-up
In addition to the commissioning instructions listed in
this chapter, the specific commissioning instructions
listed in the installation instructions for the Daikin
Altherma EHS(X/H) must be complied with.
The RoCon system offers a very wide range of application and
extension possibilities.
The individual RoCon system components communicate via the
CAN data bus. For this reason, the circuit boards RoCon BM1
and the control units RoCon B1 of the Daikin
Altherma EHS(X/H), and possibly the optional system compo-
nents room station EHS157034 and mixer module EHS157068
are connected together via data bus lines.
These system components must be allocated unique functional
IDs, so that the data exchange and the allocation functions
without any problems within the RoCon system.
4.1 Fundamental aspects of the IDs and authorisations in the RoCon system
In the RoCon system, the following functional IDs exist, which are
relevant for data exchange of the RoCon system components:
ID / function
Heating circuit IDs
Unique numbering of a heating circuit
in the heating system in the RoCon
system. A maximum of 16 heating cir-
cuits can be controlled.
Heat generator ID
Unique numbering of a heat gen-
erator in the RoCon system.
Terminal ID
Unique numbering of a control unit
RoCon B1 or EHS157034, from
which a heat generator and / or a
mixer module in the RoCon system
can be controlled remotely.
The authorisation for remote control
can be allocated to up to 10 control
units in the RoCon system. If remote
control in the RoCon system is to be
possible, then the control unit must
be allocated the ID "0".
Operating instructions
32
System components
Daikin Altherma EHS(X/H)
(RoCon BM1)
Room station EHS157034
Mixer module EHS157068
Daikin Altherma EHS(X/H)
(RoCon BM1)
1)
Mixer module EHS157068 [Boiler Assignment]
Daikin Altherma EHS(X/H)
(RoCon BM1)
Room station EHS157034
In many applications, nothing needs to be changed on the basic
settings. The more RoCon system components that are inte-
grated in the RoCon system, the more adjustments that need to
be made during the initial commissioning or when extending the
heating system.
The allocation of the functional IDs is easiest carried out via the
installation menu "Setup Wizard". Most IDs can also be adapted
subsequently to the conditions by means of individual parameter
settings in the specific parameter levels (see chapter 6).
a) If no optional RoCon system components are connected
to the Daikin Altherma EHS(X/H), in the RoCon system, just
the circuit board RoCon BM1 and the integrated control unit
RoCon B1 communicate with each other.
Adaption of the IDs is not necessary.
The question displayed during initial commissioning "Use
standard configuration?" can be confirmed by "Yes".
b) If optional RoCon system components such as
EHS157034 and / or EHS157068 are connected, adaption to
the IDs may be necessary.
Parameter
[Unmixed Circ Config]
Factory setting = 0
See tab. 6-14
Should not normally be changed.
[HC Assignment]
Factory setting = Off
See tab. 6-1
Adaption necessary because there are dif-
ferent heating circuits in the system and /
or the parameter [Master-RoCon] = On
[HC Assignment]
Factory setting = Off
See tab. 6-15
Must always be adapted to the setting of
the address switch (fig. 4-2).
[BUS ID HS]
Factory setting = 0
See tab. 6-14
Should not normally be changed.
Factory setting = 0
See tab. 6-15
Should not normally be changed.
Defines the heat generator that supplies
the allocated heating circuit with heat.
[Terminaladress]
Factory setting = Off
See tab. 6-1
The value should be set to "0" if at least 1
mixer module is connected in the RoCon
system, and the mixer circuit is to be op-
erated from the heat generator.
[Terminaladress]
Factory setting = Off
see tab. 6-1 or
The value must be set to a unique nu-
tab. 6-15 - depending
merical value in the RoCon system, if the
on the set heating cir-
room station system components are to be
cuit ID and the current
remotely controlled using a valid device ID.
operating mode
Comments
1)
1)
1)
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016