Daikin EHS157034 Operating Instructions Manual page 55

Hide thumbs Also See for EHS157034:
Table of Contents

Advertisement

Parameter
Start T-Out Cooling
Can be used only if the assigned heat generator has a cooling function
Only if parameter [HC Function] = 0:
Setting from which outside temperature the cooling operation with the highest cooling infeed
target temperature [T-Flow Cooling start] starts (setting condition: operating mode "Cool-
ing").
Max T-Out Cooling
Can be used only if the assigned heat generator has a cooling function
Only if parameter [HC Function] = 0:
Setting to determine from which outdoor temperature the lowest cooling flow temperature 
[T-Flow Cooling max] is stipulated (setting condition: operating mode "Cooling").
T-Flow Cooling start Can be used only if the assigned heat generator has a cooling function
Only if parameter [HC Function] = 0:
Setting the cooling inflow target temperature at the start of cooling mode (outside tempera-
ture = parameter [Start T-Out Cooling]).
T-Flow Cooling max Can be used only if the assigned heat generator has a cooling function
Only if parameter [HC Function] = 0:
Setting the minimum cooling inflow target temperature. This is kept constant relative to the
outside temperature (parameter [Max T-Out Cooling]).
Min T-Flow Cooling
Can be used only if the assigned heat generator has a cooling function
Only if parameter [HC Function] = 0:
Setting the absolute lower limit of the cooling inflow target temperature. The limitation is ef-
fective if a lower cooling inflow target temperature is determined based on other parameter
settings.
T-Flow Cooling
Can be used only if the assigned heat generator has a cooling function
Only if parameter [HC Function] = 1:
Setting the cooling inflow target temperature (fixed value) when cooling mode is active.
Cooling Setpoint adj Can be used only if the assigned heat generator has a cooling function
Parallel displacement of the cooling characteristic curve to match the set value.
Relay Test
See Section 6.2.2, tab. 6-2.
Screed
Function for screed drying
Off: Deactivated
On: The flow temperature is regulated according to the set screed programme. The day on
which the screed function is activated does not count towards the running time of the screed
programme. The first day starts as the day changes on the first day at 00:00. On the day of
activation we heat for the remaining time at the inflow temperature for the first day's program
(see section 3.6.13).
Screed Program
Setting the procedural program for screed heating. An individual inflow temperature can be
set for each day for a maximum period of 28 days. The end of the screed programme is de-
fined by the 1st. Day at target value setting "- - - -" (see chapter 3.6.13).
Tab. 6-16
Parameter in rotary switch setting "Configuration" level "Mixer Config"
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Description
6
x
Parameter settings
Access
Setting range
Min / Max
BE
HF
.
E
E
20 - 45 °C
.
E
E
20 - 45 °C
.
E
E
5 - 25 °C
.
E
E
5 - 25 °C
.
N
E
5 - 25 °C
.
E
E
8 - 30 °C
.
N
E
-5.0 to +5.0 kW
N
E
N
E
Off
On
N
E
10 - 70 °C per
heating day
Factory
Increment
setting
24 °C
1 °C
35 °C
1 °C
18 °C
1 °C
18 °C
1 °C
18 °C
1 °C
18 °C
1 °C
0.0 K
1 K
-
Off
-
See
1 °C
tab. 3-11