Introduction
3.1 Component specification according to UL
3.1
Component specification according to UL
The inverters have UL approval according to UL508C and CSA C22.2 No. 274-13.
Further information and a link for downloading the appropriate certificates can be found in
the following Section:
3.2
Permissible motors
Note
Motors for inverter operation
Only use motors that are suitable for operation with inverters with a DC link.
Motors for 200 V Power Modules
For the 200 V Power Modules, induction motors are permissible in the range from
25% ... 150% of the inverter power without any restrictions.
Motors for 400 V Power Modules
For the 400 V Power Modules, induction motors are permissible in the range from
25 % ... 150 % of the inverter power without any restrictions.
Motors for 690 V Power Modules
For the 690 V Power Modules, induction motors are permissible in the range from 50
% ... 150 % of the inverter power without any restrictions.
20