Siemens SINAMICS PM240-2 Hardware Installation Manual page 34

Power module for sinamics g120
Hide thumbs Also See for SINAMICS PM240-2:
Table of Contents

Advertisement

Installing/mounting
4.4 Mounting the Power Modules
Depth with Control Unit and Operator Panel (mm)
FSA ... FSC
FSD ... FSF
Table 4- 2
Frame
size
FSA
FSB
FSC
FSD
FSE
FSF
The Power Modules are designed for mounting without any lateral cooling air clearance. For toler-
1)
ance reasons, we recommend a lateral clearance of approx. 1 mm.
34
With Control Unit:
With Control Unit and blanking cover / BOP-2:
With Control Unit and IOP:
With Control Unit:
With Control Unit and blanking cover / BOP-2:
With Control Unit and IOP:
Drilling dimensions, cooling air clearances [mm] and fixing [Nm]
Drilling dimensions
h
b
186
62.3
281
80
343
120
430
170
509
230
680
270
CU230P-2
Cooling air clearances
c
Top
Bottom
6
80
100
6
80
100
6
80
100
7
300
350
8.5
300
350
13
300
350
Hardware Installation Manual, 01/2017, A5E33294624B AE
CU240B/E-2
+ 59
+ 41
+ 70
+ 52
+ 81
+ 63
+ 15.5
+ 0
+ 26.5
+ 8.5
+ 37.5
+ 19.5
Fixing/torque
1)
Front
100
3 x M4 / 2.5
100
4 x M4 / 2.5
100
4 x M5 / 3.5
100
4 x M5 / 6.0
100
4 x M6 / 10
100
4 x M8 / 25
Power Module PM240-2
CU250S-2
+ 62
+ 73
+ 84
+ 18.5
+ 29.5
+ 40.5

Hide quick links:

Advertisement

Table of Contents
loading