Siemens SINAMICS PM240-2 Hardware Installation Manual page 22

Power module for sinamics g120
Hide thumbs Also See for SINAMICS PM240-2:
Table of Contents

Advertisement

Installing/mounting
4.1 Installation conditions
● Carefully note that for plants and systems in conformance with UL/cUL, the line and
output voltage may not be higher than 600 V.
● Only use copper cables rated for 60 °C or 75 °C.
● For frame size FSE inverters, use only cables certified for temperatures of 75° C to
connect the braking resistor.
● The DC-link terminals, DCP and DCN, were not investigated regarding conformance with
UL/cUL.
Additional requirements for CSA compliance, frame sizes FSA ... FSC
Install the inverter with an external suppression device with the following properties:
● Surge protection device with the appropriate certification (category checking numbers
VZCA and VZCA7)
● Rated supply voltage
– 240 V (phase with respect to ground), 240 V (phase to phase) for 200 V inverters
– 480 V (phase with respect to ground), 480 V (phase to phase) for 400 V inverters
● Terminal voltage, V
● Suitable for SPD applications, type 1 or type 2
Alternatively, use a surge protection device, article number 5SD7 424-1 from Siemens AG.
Additional requirements relating to CSA conformance, frame sizes FSD ... FSF
Overvoltage category OVC III must be ensured for all connections of the power circuit. This
can mean that a surge suppressor must connected upstream on the line side. The rated
voltage of the surge suppressor must not exceed the line voltage, and must guarantee the
limit values (VPR) specified here.
Line voltage
3 AC 200 V ... 240 V
3 AC 380 V ... 480 V
3 AC 500 V ... 600 V
22
= 2000 V
PR
Grounded neutral conductor
Grounded line conductor
Grounded neutral conductor
Grounded line conductor
Grounded neutral conductor
Grounded line conductor
Phase to ground
Rated
VPR
voltage
139 V
2.5 kV
240 V
4 kV
277 V
4 kV
480 V
6 kV
347 V
6 kV
600 V
6 kV
Hardware Installation Manual, 01/2017, A5E33294624B AE
Phase to phase
Rated
VPR
voltage
240 V
4 kV
240 V
4 kV
480 V
4 kV
480 V
4 kV
600 V
4 kV
600 V
4 kV
Power Module PM240-2