The Transducer Block

3.3 Default configuration

3.3
Default configuration
The default configuration of SITRANS TH400 will suite the customer's demand in many
cases. The configuration task has thus been reduced considerably.
The individual default configurations are shown in the TB Parameter List, but in short the
default configuration is as follows:
3.4

Your application set up.

In the Transducer block all parameters marked R / W can be adapted to suit any
measurement in temperature, ohm or mV. The way of presenting the file data mentioned in
the introduction varies greatly from one piece of application software to the other. Some
programs show drop down menus in which the parameters must be selected via text lines,
while other programs require the user to type in the numerical value of the parameter
selection.
12
– Pt100 acc. to the standard
EN 60751
°C
3-wire connection
Only sensor 1
No sensor error detection
(chapter 3.8.1 LIN_TYPE, value 102)
(chapter 3.8.1 PRIMARY_VALUE_UNIT, value 1001)
(chapter 3.8.2 SENSOR_CONNECTION, value 1)
(chapter 3.8.4 SENSOR_MEAS_TYPE, value 220)
(chapter 3.8.7 SENSOR_WIRE_CHECK_1, value 3)
Configuration Manual, 02/2007, A5E01039143-01