Siemens SITRANS TH400 PROFIBUS PA Configuration Manual page 22

Temperature
Table of Contents

Advertisement

The Transducer Block
3.6 Transducer Block Examples Setup
Example:
The coordinates for converting the signal from a logarithmic potentiometer to a linear signal.
TAB_ACTUAL_NUMBER
TAB_XY_VALUE1
TAB_XY_VALUE2
TAB_XY_VALUE3
TAB_XY_VALUE4
TAB_XY_VALUE5
TAB_XY_VALUE6
TAB_XY_VALUE7
TAB_XY_VALUE8
TAB_XY_VALUE9
TAB_XY_VALUE10
(Output will readout 325% with 1.0% potentiometer value)
22
= 10 (number of linearisation points to follow up to max 50)
= 0,0; -100
= 0,1; 0
= 0,2; 100
= 0,4; 200
= 0,8; 300
= 1,6; 400
= 3,2; 500
= 6,4; 600
= 12,8; 700
= 25,6; 800
SITRANS TH400 PROFIBUS® PA
Configuration Manual, 02/2007, A5E01039143-01