FORM-C OPERATION

Typical Form-A and Form-C (KYZ) Connections

A Form-C (KYZ) switch is often used so that a defective switch or associated wiring can be
detected. In the illustration alarm sensing or pulse counting is performed on the "INPUT-1"
connection only. "INPUT-2" is used for fault detection.
The switches should never be open or closed at the same time. If so the CNI2 will report an
alarm condition. The next figure shows how a KYZ fault is detected.

Example of Detection of a Form-C Fault

111