SPM Flex Gas Detector
Ethernet connector
Input power
connections
Figure 8. SPM Flex connections
Terminal Module
The terminal module is located on the main PCB inside the gas detector� All
power, relay, and 4-20 mA connections to SPM Flex are made via this module�
Wire entry to the terminal module area is via the cable entry/conduit entry located
at the top of the detector�
This table shows the default wiring configuration for the communication
connector when installed by Honeywell Analytics� The relays are labeled for the
factory default but the configuration can be modified to have a single alarm and
separate faults�
Relay Terminal Connections
No.
Color
Assign to Relay
1
Brown
Alarm2 COM
2
Red
Alarm2 NO
3
Orange
4
Yellow
Alarm1 COM
5
Green
Alarm1 NO
6
Blue
7
Purple
Fault COM
8
Gray
9
White
10
Black
For 4-20 mA wiring, wires 1 through 8 would be disconnected and wires 9 and 10
would be used� Do not run 4-20 mA signals and relay signals in the same cable
bundle�
20
P8
Relay
connections
NC
NC
Fault NO
NC
NC
P9
4-20 mA
connections
top of
detector