59 MAINTENANCE
WARNING
The operations described below shall always be performed
with the boiler and the power supply switch off.
The boiler front panel has to be removed to access the
various devices to be maintained and checked.
1. Unhook the front panels and remove.
Cleaning the Casing Material
Use a soapy solution and sponge only. Rinse with clean
water and dry with chamois leather or soft cloth.
60 CLEANING THE FLUEWAYS
1. Close off the fuel supply to the burner.
2. Ensure that the boiler has been cooled
to ambient temperature.
3. Isolate the mains supply to the boiler
and burner.
4. Disconnect the cable and supply pipe
to the burner.
5. Open the combustion chamber (four
nuts) and flue way (three nuts) doors
by removing the nuts.
6. Remove the flue way baffles.
7. Thoroughly clean the flue ways and
baffles.
8. Release and allow to swing down the
rear cleanout covers by undoing the two
upper nuts and loosening the two lower
nuts. Dispose of the debris/soot that
may have accumulated.
9. Replace the rear cleanout covers after
first inspecting and if necessary
replacing the seal.
10. Brush out the combustion chamber
and vacuum the soot from beneath the
flue ways.
11. Replace the flue baffles into the flue
ways (refer to Frame 22 for number
and location).
12. Check the condition of the combustion
chamber door insulation and replace if
necessary.
13. Check the condition of the combustion
chamber door seal and replace if
necessary.
14. Refer to the burner manufacturer's
Instructions for burner maintenance.
36
INSTALLATION
vic7114
vic7116
Brush
Brush and
vacuum cleaner
Vacuum
cleaner
Viceroy GT -
Installation & Servicing
Vacuum
cleaner