10 FLUING

According to the output, the difference between the temperature of
the flue gas and the ambient temperature can be as low as 160ºC.
The installer will have to respect all of the usual precautions (dilution
- piping - T for removal of condensation) in order to prevent
deterioration of the chimney. The use of a draught stabiliser is also
recommended.
FLUE SIZE
Refer to applicable regulations while determining the size and height
of the flue. Please note that Viceroy GT boilers have pressurised
and sealed combustion chambers and that the pressure at the outlet
must not exceed 0 mbar.
Detailed recommendations relating to the design of flues for GAS
fired appliances are quoted in BS. 6644 and IGE/UP/10, whilst BS.
5410 Pt. 1 similarly applies to OIL fired boilers.
The table below contains the minimum dimensions of the flue
required for each boiler model in order to ensure sufficient draught
at the outlet.
Boiler
GT 8
GT 9
GT 10
GT 11
GT 12
GT 13
GT 14
(1) : at boiler maximum input.
(2) : Boiler flow temperature: 80ºC (ambient temperature : 20ºC).
11 DIMENSIONAL INFORMATION REQUIRED FOR THE FLUE CONNECTION
Connection
The connection must be made in a competent
manner with airtight pipe in a material that is
resistant to hot gases from the combustion and
possible acid condensation. This pipe must be
as short as possible, be removable and without
any sudden change in its section.
The diameter must always be at least equal to
that of the boiler outlet.
12
INSTALLATION
Heat
Required
Output
Draught
kW
mbar
390
0
450
0
540
0
600
0
670
0
720
0
780
0
However, care must be taken to comply with any
applicable national or local regulations.
Mass Flow of Flue Gases
kg/s
Fuel Oil
Natural Gas
13% CO
9.5% CO
2
2
0.184
0.193
0.212
0.223
0.255
0.267
0.283
0.297
0.316
0.332
0.340
0.357
0.368
0.386
1000mm min.
45
Flue Gas
Chimney:
Temperature
Minimum
(1) (2)
Recommended
Diameter
ºC
Ø min
m m
220
250
220
250
220
250
220
300
220
300
220
300
220
300
130
1013
Viceroy GT -
Installation & Servicing