46 CONNECTING OPTIONAL FEATURES - FD168 Deluxe Control Panel
Circulating Pump
The CH circulating pump should be connected across
terminals 8, 9 and 10.
Shunt Pump
The shunt pump should be connected across terminals 11, 12
and 13.
Flow Switch / Optional Safety Device
If a flowswitch or other safety control is to be included in the
system, connect the device(s) in series in the safety circuit,
across terminals 14 and 15.
Burner Alarm Indicator
If an alarm indicator is to be included it should be connected
across terminals 6 and 7.
Safety Thermostat Alarm Indicator
If an alarm indicator is to be included it should be connected
across terminals 4 and 5.
47 FITTING OPTIONAL FEATURES - FD168 Deluxe Control Panel
Hours Run Meters (IC8)
One or two optional hours run meters (stage 1
and 2) may be fitted on the front of the control
panel.
Proceed as follows:
1. Cut the cover with a cutter along the edges
of the coloured rectangle.
2. Pull out the two wires standing by in the
control panel.
3. Connect the wires to the hours run meter
(the wires are interchangeable).
4. Clip the hours run meter into the control
panel.
If the burner is a one-stage burner, the counter
displays the burner operating time.
If the burner has two stages, the hours run
meters display the operating time of each
stage.
Flue Gas Thermometer (ID28)
An optional flue gas thermometer may be fitted
on the front of the control panel.
Proceed as follows:
1. Cut the cover with a cutter along the edges
of the coloured rectangle.
2. Clip the thermometer into the opening.
3. Route the sensor to the back of the boiler
via the cable channel and insert it in the flue
gas pipe.
Viceroy GT -
Installation & Servicing
INSTALLATION
1
2
L
N
ALI
230V 50Hz
6 A
3
3
4
5
6
7
8
9
10
11
12
L
N
L
N
L
N
NL
VA - TS
VA
6 A
2
1
2
13
14 15
14 15
CS
Remove white
link wire
1
4
3
29

Advertisement

Table of Contents
loading

Table of Contents