Technical functions
600-605 Operating Data
Value:
Par. no.
Description
600
Operating hours
601
Hours run
602
kWh counter
603
Number of power-up's
604
Number of overtem-
peratures
605
Number of overvolt-
ages
Function:
These parameters can be read out via the serial
communication port and the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the frequency converter
has been operating. The value is saved every hour
and when there is a mains failure. This value cannot
be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been oper-
ating since the reset in parameter 619 Reset of
hours-run counter. The value is saved every hour
and when there is a mains failure.
Parameter 602, kWh counter:
Gives the frequency converter's output energy in
kWh. The calculation is based on the mean kW
value over one hour. This value can be reset using
parameter 618 Reset of kWh counter.
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage
undertaken on the frequency converter.
Parameter 604, Number of overtemperatures:
Gives the number of overtemperature faults that
have been registered on the frequency converter's
heat sink.
Parameter 605, Number of overvoltages:
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.A1.02 - VLT is a registered Danfoss trade mark
®
VLT
Display text
(OPERA TING HOURS)
(RUNNING HOURS)
(KWH COUNTER)
(POWER UP'S)
(OVER TEMP'S)
(OVER VOLT'S)
Gives the number of overvoltages of the intermedi-
ate circuit voltage in the frequency converter. This is
only counted when Alarm 7 Overvoltage is active.
NB!:
Parameters 615-617 Fault log can-
not be read out via the integral control unit.
615 Fault log: Error code
615
(F.LOG: ERROR COD)
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for
a trip (cut-out of the frequency converter) occurring.
10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most
recently saved data value. The highest log number
[10] contains the oldest data value saved. If a trip
occurs, it is possible to see the cause, time and a
possible value of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to
a table. See the table in Warnings/alarm messages.
616 Fault log: Time
616
(F.LOG: TIME)
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total num-
ber of operating hours in connection with the last 10
trips.
FCD Series
Unit
Hours
0-130,000.0
Hours
0-130,000.0
kWh
Depends on unit
Number of times
Number of times
Number of times
Range
0-9999
0-9999
0-9999
113