ABB REL670 Product Manual page 75

Line distance protection
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

Line distance protection REL670 2.2
Product version: 2.2
Table 52. Instantaneous residual overcurrent protection EFPIOC
Function
Operate current
Reset ratio
Operate time at 0 to 2 x I
set
Reset time at 2 x I
to 0
set
Critical impulse time
Operate time at 0 to 10 x I
set
Reset time at 10 x I
to 0
set
Critical impulse time
Dynamic overreach
ABB
Range or value
(5-2500)% of lBase
> 95% at (50–2500)% of lBase
Min. = 15 ms
Max. = 25 ms
Min. = 15 ms
Max. = 25 ms
10 ms typically at 0 to 2 x I
set
Min. = 5 ms
Max. = 15 ms
Min. = 25 ms
Max. = 35 ms
2 ms typically at 0 to 10 x I
set
< 5% at t = 100 ms
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
-
-
-
-
1MRK 506 372-BEN -
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents