Line distance protection REL670 2.2
Product version: 2.2
or equipment, either on the Substation Automation (SA) bus or
Substation Monitoring (SM) bus.
Available communication protocols are:
• IEC 61850-8-1 communication protocol
• IEC/UCA 61850-9-2LE communication protocol
• LON communication protocol
• SPA communication protocol
• IEC 60870-5-103 communication protocol
• DNP 3.0 communication protocol
Several protocols can be combined in the same IED.
IEC 61850-8-1 communication protocol
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in PCM600.
The IED is equipped with up to six (order dependent) optical
Ethernet rear ports for IEC 61850-8-1 station bus
communication. The IEC 61850-8-1 communication is also
possible from the electrical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from different
vendors to exchange information and simplifies system
engineering. IED-to-IED communication using GOOSE and
client-server communication over MMS are supported.
Disturbance recording file (COMTRADE) uploading can be done
over MMS or FTP.
IEC 61850 quality expander QUALEXP
The quality expander component is used to display the detailed
quality of an IEC/UCA 61850-9-2LE analog channel. The
component expands the channel quality output of a Merging
Unit analog channel received in the IED as per the IEC
61850-7-3 standard. This component can be used during the
ACT monitoring to get the particular channel quality of the
Merging Unit.
IEC/UCA 61850-9-2LE communication protocol
Optical Ethernet port communication standard
IEC/UCA 61850-9-2LE for process bus is supported.
IEC/UCA 61850-9-2LE allows Non Conventional Instrument
Transformers (NCIT) with Merging Units (MUs) or stand-alone
MUs to exchange information with the IED, and simplifies SA
engineering. IEC/UCA 61850-9-2LE uses the same port as
IEC 61850-8-1.
LON communication protocol
Existing stations with ABB station bus LON can be extended
with use of the optical LON interface (glass or plastic). This
allows full SA functionality including peer-to-peer messaging
and cooperation between the IEDs.
SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
automation systems but the main use is for Substation
Monitoring Systems SMS.
46
IEC 60870-5-103 communication protocol
A single glass or plastic port is provided for the
IEC 60870-5-103 standard. This allows design of simple
substation automation systems including equipment from
different vendors. Disturbance files uploading is provided.
Measurands for IEC 60870-5-103 I103MEAS
103MEAS is a function block that reports all valid measuring
types depending on the connected signals. The set of
connected inputs will control which ASDUs (Application Service
Data Units) are generated.
Measurands user-defined signals for IEC 60870-5-103
I103MEASUSR
I103MEASUSR is a function block with user-defined input
measurands in monitor direction. These function blocks include
FunctionType parameter for each block in the private range,
the
Information number parameter for each block.
and the
Function status auto-recloser for IEC 60870-5-103 I103AR
I103AR is a function block with defined functions for
autorecloser indications in monitor direction. This block
FunctionType parameter, and the information
includes the
number parameter is defined for each output signal.
Function status earth-fault for IEC 60870-5-103 I103EF
I103EF is a function block with defined functions for earth fault
indications in monitor direction. This block includes the
FunctionType parameter; the information number parameter is
defined for each output signal.
Function status fault protection for IEC 60870-5-103
I103FLTPROT
I103FLTPROT is used for fault indications in monitor direction.
Each input on the function block is specific for a certain fault
type and therefore must be connected to a correspondent
signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device and must be
connected to the general trip signal SMPPTRC_TRIP or
equivalent.
IED status for IEC 60870-5-103 I103IED
I103IED is a function block with defined IED functions in monitor
direction. This block uses the parameter
information number parameter is defined for each input signal.
Supervison status for IEC 60870-5-103 I103SUPERV
I103SUPERV is a function block with defined functions for
supervision indications in monitor direction. This block includes
FunctionType parameter; the information number
the
parameter is defined for each output signal.
Status for user-defined signals for IEC 60870-5-103
I103USRDEF
I103USRDEF comprises function blocks with user-defined
input signals in monitor direction. These function blocks include
the
FunctionType parameter for each block in the private range,
and the
information number parameter for each input signal.
1MRK 506 372-BEN -