Line distance protection REL670 2.2
Product version: 2.2
Table 25. Frequency influence (reference standard: IEC 60255–1)
Dependence on
Frequency dependence, operate value
Frequency dependence for distance protection operate value
Harmonic frequency dependence (20% content)
Harmonic frequency dependence for distance protection (10% content)
Harmonic frequency dependence for high impedance differential
protection (10% content)
Harmonic frequency dependence for overcurrent protection
Type tests according to standards
Table 26. Electromagnetic compatibility
Test
1 MHz burst disturbance
100 kHz slow damped oscillatory wave immunity test
Ring wave immunity test, 100 kHz
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity test
Conducted common mode immunity test
Power frequency magnetic field test
Pulse magnetic field immunity test
Damped oscillatory magnetic field test
Radiated electromagnetic field disturbance
Radiated electromagnetic field disturbance
Conducted electromagnetic field disturbance
Radiated emission
Radiated emission
Conducted emission
ABB
Within nominal range
f
±2.5 Hz for 50 Hz
r
f
±3.0 Hz for 60 Hz
r
f
±2.5 Hz for 50 Hz
r
f
±3.0 Hz for 60 Hz
r
nd
rd
th
2
, 3
and 5
harmonic of f
r
nd
rd
th
2
, 3
and 5
harmonic of f
r
nd
th
2
, 3rd and 5
harmonic of f
r
nd
rd
th
2
, 3
and 5
harmonic of f
r
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
2-4 kV, 1.2/50 ms
high energy
150-300 V, 50 Hz
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
1000 A/m
100 A/m
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m
80-1000 MHz
10 V, 0.15-80 MHz
30-5000 MHz
30-5000 MHz
0.15-30 MHz
1MRK 506 372-BEN -
Influence
±1.0%/Hz
±2.0%/Hz
±2.0%
±10.0%
±10.0%
±3.0%
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V
IEC 61000–4–9, Class V
IEC 61000-4-10, Class V
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEEE/ANSI C63.4, FCC
IEC 60255-26