ABB REL670 Product Manual page 121

Line distance protection
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

Line distance protection REL670 2.2
Product version: 2.2
Table 183. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
× +
t
B k tDef
(
)
ç
÷
P
ç
-
÷
I
1
è
ø
EQUATION1249-SMALL V2 EN
Reset characteristic:
t r
=
×
t
k
(
)
2
-
I
1
EQUATION1250-SMALL V1 EN
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
ABB
Range or value
0.10 ≤ k ≤ 2.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=28.2, B=0.1217, P=2.0 , tr=29.1
A=19.61, B=0.491, P=2.0 , tr=21.6
A=0.0086, B=0.0185, P=0.02, tr=0.46
A=0.0515, B=0.1140, P=0.02, tr=4.85
A=64.07, B=0.250, P=2.0, tr=30
A=28.55, B=0.712, P=2.0, tr=13.46
A=0.086, B=0.185, P=0.02, tr=4.6
1MRK 506 372-BEN -
Accuracy
ANSI/IEEE C37.112 ,
±5.0% or ±160 ms
whichever is greater
121