ABB REL670 Product Manual page 117

Line distance protection
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

Line distance protection REL670 2.2
Product version: 2.2
Basic IED functions
Table 174. Self supervision with internal event list
Data
Recording manner
List size
Table 175. Time synchronization, time tagging
Function
Time tagging accuracy of the synchrophasor data
Time tagging resolution, events and sampled measurement values
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled
measurement values
Time tagging error with SNTP synchronization, sampled measurement values
Table 176. Time synchronization PTP: IEC/IEEE 61850-9-3
Supported types of clock
Accuracy
Number of nodes
Ports supported
Table 177. GPS time synchronization module (GTM)
Function
Receiver
Time to reliable time reference with antenna in new
position or after power loss longer than 1 month
Time to reliable time reference after a power loss longer
than 48 hours
Time to reliable time reference after a power loss shorter
than 48 hours
Table 178. GPS – Antenna and cable
Function
Max antenna cable attenuation
Antenna cable impedance
Lightning protection
Antenna cable connector
Accuracy
ABB
Value
Continuous, event controlled
40 events, first in-first out
Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)
According to standard IEC/IEEE 61850-9-3
According to standard IEC/IEEE 61850-9-3
All rear Ethernet ports
Range or value
Accuracy
±1µs relative UTC
<30 minutes
<15 minutes
<5 minutes
1MRK 506 372-BEN -
Value
± 1 µs
1 ms
± 1.0 ms typically
± 1.0 ms typically
Value
26 db @ 1.6 GHz
50 ohm
Must be provided externally
SMA in receiver end
TNC in antenna end
+/-1μs
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents