Line distance protection REL670 2.2
Product version: 2.2
Logic
Table 97. Tripping logic common 3-phase output SMPPTRC
Function
Trip action
Minimum trip pulse length
3-pole trip delay
Evolving fault delay
Table 98. Number of SMPPTRC instances
Function
SMPPTRC
Table 99. Number of SMAGAPC instances
Function
SMAGAPC
Table 100. Number of STARTCOMB instances
Function
STARTCOMB
Table 101. Number of TMAGAPC instances
Function
TMAGAPC
Table 102. Number of ALMCALH instances
Function
ALMCALH
Table 103. Number of WRNCALH instances
Function
WRNCALH
Table 104. Number of INDCALH instances
Function
INDCALH
ABB
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.020-0.500) s
(0.000-60.000) s
3 ms
12
3 ms
12
3 ms
32
3 ms
6
3 ms
-
3 ms
-
3 ms
-
Accuracy
-
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
±0.2% or ±15 ms whichever is greater
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
6
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
-
Quantity with cycle time
8 ms
5
1MRK 506 372-BEN -
100 ms
-
100 ms
-
100 ms
-
100 ms
-
100 ms
5
100 ms
5
100 ms
-