Line distance protection REL670 2.2
Product version: 2.2
Auxiliary DC voltage
Table 14. PSM - Power supply module
Quantity
Auxiliary DC voltage, EL (input)
Power consumption
Auxiliary DC power in-rush
Binary inputs and outputs
Table 15. BIM - Binary input module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
ABB
Rated value
EL = (24-60) V
EL = (100-250) V
50 W typically
< 10 A during 0.1 s
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1–20 ms
1MRK 506 372-BEN -
Nominal range
EL ±20%
EL ±20%
-
-
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-