ABB REL670 Product Manual page 56

Line distance protection
Hide thumbs Also See for REL670:
Table of Contents

Advertisement

Line distance protection REL670 2.2
Product version: 2.2
Table 16. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
Table 17. IOM - Binary input/output module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
56
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
Rated value
8
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Settable 1-20 ms
1MRK 506 372-BEN -
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
ABB