[F14] Error TTW sensor failure
TTW sensor
connector (CN214) is
connected
TTW sensor
characteristic is normal
Replace water heat exchange control board
[F17] Error TFI sensor failure
TFI sensor
connector (CN213) is
connected
TFI sensor
characteristic is normal
Replace water heat exchange control board
[F18] Error THO sensor failure
THO sensor
connector (CN206) is
connected
THO sensor
characteristic is normal
Replace water heat exchange control board
AMP Air Conditioning
Start
No
Yes
No
(Refer to Characteristic table on page 113)
Yes
Start
No
Yes
No
(Refer to Characteristic table on page 113)
Yes
Start
No
Yes
No
(Refer to Characteristic table on page 113)
Yes
97
www.ampair.co.uk | sales@ampair.co.uk
Correct TTW sensor
connection
Replace TTW sensor
Correct TFI sensor
connection
Replace TFI sensor
Correct THO sensor
connection
Replace THO sensor