9-6-2. Outdoor unit
No.
Component name
Compressor
Type
DA422A3F-26M
1
Outdoor fan motor
Type
ICF-280-A100-1
2
4-way valve coil
Type
3
STF-H01AP1874A1
2-way valve coil
4
Pulse motor valve coil
Type
UKV-A038
5
AMP Air Conditioning
Measure the resistance value of each winding with a tester.
Red
White
Black
Measure the resistance value of each winding with a tester.
Red
White
Black
Measure the resistance value.
P804, P1104HR-E1
1617 Ω ± 113 Ω
Measure the resistance value.
P804, P1104HR-E1
1435 Ω ± 144 Ω
1 Black
M
6 Grey
3 Red
Yellow
Grey
Orange
2
6
116
Check procedure
Resistance
Location
−
1.04-1.16 Ω
Red
White
−
1.04-1.16 Ω
White
Black
−
1.04-1.16 Ω At 20 °C
Black
Red
Location
−
Red
White
−
P804,
White
Black
P1104HR-E1
−
Black
Red
Location
−
Grey
Black, Red
−
Grey
Yellow, Orange
4
www.ampair.co.uk | sales@ampair.co.uk
value
Resistance value
14.8 ± 1.5 Ω
Resistance
value
43-49 Ω
43-49 Ω
Condition 20 °C