Toshiba HWS-P804XWHM3-E1(TR) Service Manual page 107

Air to water heat pump
Table of Contents

Advertisement

Outdoor LED
Check code
indication
[P15]
<Indication 1> <Indication 2>
AMP Air Conditioning
(No specific description indicates outdoor unit parts.)
[Gas leakage detection]
No gas leakage.
Appropriate refrigerant amount.
Pulse motor valve is normal.
Service valve is fully opened.
Piping collapse
Temperature sensor check
Discharge sensor CN603
Suction sensor CN600
Check outdoor control board
If defective, replace it
106
Check and Action procedure
PC board
P804HR-E1, P1104HR-E1 (MCC-1571)
www.ampair.co.uk | sales@ampair.co.uk
Correct defective portion
Re-charge refrigerant
Correct defective portion
Replace defective parts
Open fully service valve
Repair or replace pipe
Correct connector
Replace sensor

Advertisement

Table of Contents
loading

Table of Contents