Toshiba HWS-P804XWHM3-E1(TR) Service Manual page 48

Air to water heat pump
Table of Contents

Advertisement

Item
8-2.
13) Night time low-noise operation
Operation Mode
A night time low-noise operation reduces operation frequency and the number of outdoor fan rotations for a certain period
and Control
during night time as noise control for urban operation.
Method
Maximum operation frequency 40.2 Hz (Hot water supply/Heating/Cooling)
Maximum fan tap
The night time low-noise operation is enabled / disabled by changing the remote controller FC_09.
<How to set> - Refer to "11. Night time Low-noise Setting" on page 131.
1) Press the TEMP.
noise setting mode)
The Code No. field displays "09", and the DATA "0000",
2) Press TIME
Pressing SET
(When "1" as enable is set, the night time low-noise setting is enabled, the control starts at the set start time.)
3) Press TEST
original status.
AMP Air Conditioning
Operation flow and applicable data, etc.
500 rpm (P804HR-E1, P1104HR-E1)
and TEST
button at the same time for 4 seconds or longer. (Shifted to the night time low-
to set enable "1" or disable "0".
change DATA and
display to be lit and the setting is confirmed.
to exit the night time low-noise time setting mode. The
47
, and
being displayed blink.
and
goes out, returning to its
www.ampair.co.uk | sales@ampair.co.uk

Advertisement

Table of Contents
loading

Table of Contents