Toshiba HWS-P804XWHM3-E1(TR) Service Manual page 121

Air to water heat pump
Table of Contents

Advertisement

Function code table
FC
01
Water heat exchanger capacity *1
02
Cooling/Non-cooling switching
08
Hot Water Boost operation time (operating time)
09
Hot Water Boost set temperature
0A
Anti bacteria set temperature
0B
Anti bacteria holding time
0C
Mixing valve drive time
0F
Hot water HP allowance while cooling + hot water
supply
18
Upper limit of cooling set temperature
19
Lower limit of cooling set temperature
1A
Upper limit of heating (ZONE1) set temperature
1B
Lower limit of heating (ZONE1) set temperature
1C
Upper limit of heating (ZONE2) set temperature
1D
Lower limit of heating (ZONE2) set temperature
1E
Upper limit of hot water set temperature
1F
Lower limit of hot water set temperature
20
Hot water HP start temperature
21
Hot water HP stop temperature
22
Priority mode Hot water supply/Heating switching
temperature
23
Boiler output enable switching temperature
24
Outside air temperature for hot water temperature
compensation start
25
Hot water temperature compensation value
26
Night set back change temperature range
27
Set temperature shift with heating Auto
29
Outside air temperature T1 temperature
2B
Outside air temperature T3 temperature
2C
Set temperature A with outside air temperature of T0
2D
Set temperature B with outside air temperature of T1
2E
Set temperature C with outside air temperature of 0 °C 0020: 20 °C
2F
Set temperature D with outside air temperature of T3
30
Set temperature E with outside air temperature of 20 °C 0020: 20 °C
31
Zone2 ratio with Zone1 as Auto
33
Hydro unit backup heater down time
34
Hydro unit backup heater up time
3A
Frost protection function Invalid/Valid
3B
Frost protection set temperature
3C
2-way valve operation (logical reverse) control
3E
Heating HP/Boiler priority switching when using boiler
40
Activate/deactivate room temperature control
*1 FC_01 is needed for PCB replacement or function code reset procedure has been completed.
*2 System restart with remote controller.
*3 Restart in the mode when stopping.
*4 In addition, it is enable only when switch 2-3 is set to "OFF" and FC61 is set to "3".
AMP Air Conditioning
Item
Details
0012: P804XWH**-E1
0015: P1104XWH**-E1 Depends on type
0000: Cooling
0001: Not cooling
0003: 30 min
-
0018: 180 min
0040: 40 °C
-
0080: 80 °C
0065: 65 °C
-
0080: 80 °C
0000: 0 min
-
0060: 60 min
0003: 30 sec
-
0024: 240 sec
0000: Not allow
-
0001: Allow
0018: 18 °C
-
0030: 30 °C
0007: 7 °C
-
0018: 20 °C
0037: 37 °C
-
0060: 60 °C
0020: 20 °C
-
0037: 37 °C
0037: 37 °C
-
0060: 60 °C
0020: 20 °C
-
0037: 37 °C
0060: 60 °C
-
0080: 80 °C
0040: 40 °C
-
0060: 60 °C
0020: 20 °C
-
0045: 45 °C
0040: 40 °C
-
0050: 50 °C
-0020: -20 °C
-
0020: 20 °C
-0020: -20 °C
-
0020: 20 °C
-0020: -20 °C
-
0010: 10 °C
0000: 0K
-
0015: 15K
0003: 3K
-
0020: 20K
-0005: -5K
-
0005: 5K
-0015: -15 °C
-
0000: 0 °C
0000: 0 °C
-
0015: 15 °C
0020: 20 °C
-
0060: 60 °C
0020: 20 °C
-
0060: 60 °C
-
0060: 60 °C
0020: 20 °C
-
0060: 60 °C
-
0060: 60 °C
0000: 0%
-
0100: 100%
0000: 5 min
0001: 10 min
0002: 15 min
0003: 20 min
0000: 10 min
0001: 20 min
0002: 30 min
0003: 40 min
0000: Invalid
0001: Valid
0008: 8 °C
-
0020: 20 °C
0000: Energised during cooling
0001: Not energised during cooling
0000: Priority on HP
0001: Priority on boiler
0000: Deactivate
0001: Activate
120
www.ampair.co.uk | sales@ampair.co.uk
Factory default
0000: Cooling
0006: 60 min
0075: 75 °C
0075: 75 °C
0030: 30 min
0006: 60 sec
0000: Not allow
0025: 25 °C
0007: 7 °C
0060: 60 °C
0020: 20 °C
0060: 60 °C
0020: 20 °C
0075: 75 °C
0040: 40 °C
0038: 38 °C
0045: 45 °C
0000: 0 °C
-0010: -10 °C
0000: 0 °C
0003: 3K
0005: 5K
0000: 0K
-0010: -10 °C
0010: 10 °C
0040: 40 °C
0035: 35 °C
0030: 30 °C
0025: 25 °C
0020: 20 °C
0080: 80%
0001: 10 min
0000: 10 min
0001: Valid
0015: 15 °C
0000: Activate during
cooling
0000: Priority on HP
0000: Deactivate