14. Failure History Calling Function
<Details>
This function calls the previous failure details.
<Procedure>
1
Press the TEST
for 4 seconds or longer to call the service check mode.
The service check lights up with CODE No. "01" displayed at first,
and the latest warning detail is displayed. The warning details of the
current warning is displayed.
2
To monitor other failure history, press the TEMP.
button for temperature setting to change the
failure history number (item code).
Item code "01" (Latest) ---> Item code "01" (Old)
Note: The failure history contains the last 4 failures.
3
Pressing the TEST
display.
NOTE
Do not press the CL
If the button is pressed and the history is deleted, perform power cycle.
If the current failure is the same as the one occurred last time before deleted, the history may not record the current
failure.
AMP Air Conditioning
and SET
buttons at the same time
(See display
button returns to the normal
button. Pressing the button deletes all the failure history of the hydro unit.
)