Fujitsu AUXB04GALH Service Manual page 130

Airstage j-iiil series
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

Trouble shooting 52
OUTDOOR UNIT Error Method:
High Pressure Switch Error
Detective Actuators:
High pressure switch
Forecast of Cause :
1. High pressure switch connector disconnection, open
2. High pressure switch characteristics defective
3. Main PCB defective
Check Point 1 : Check the high pressure switch connection state
Connector and wiring connection state check
Cable open check
OK
Check Point 2 : Check the high pressure switch characteristics
Switch characteristics check
* For the characteristics of high pressure switch, refer to the "Service Parts Information 16".
OK
Check Point 3 : Replace Main PCB
Change Main PCB and set up the original address.
Indicate or Display:
E. 86.4
Outdoor Unit : E. 86. 4
Indoor Unit
Error Code
Detective details:
When the power was turned on, "high pressure switch : open" was detected.
: Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
: 86