Fujitsu AUXB04GALH Service Manual page 102

Airstage j-iiil series
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

Trouble shooting 24
INDOOR UNIT Error Method:
Indoor unit suction air temp.
thermistor error (Outdoor Air unit )
Detective Actuators:
Indoor Unit Controller PCB Circuit
Suction air temp. Sensor
Forecast of Cause : 1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check sensor resistance value
Sensor Characteristics (Rough value)
Temperature (°C)
Resistance Value (
Temperature (°C)
Resistance Value (
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage CN9 of Controller PCB (DC5.0V)
If the voltage does not appear, replace Controller PCB and set up the original address.
Indicate or Display:
E.4.A.1
Outdoor Unit : E.5 U.1
Error Code
Detective details:
When Indoor unit suction air temp. thermistor open or shortage is detected
0
5
1
)
33.6
25.2
20.1
4
0
4
5
5
)
5.3
4.3
3.5
: 4 A, 4 A. 1
0
1
5
2
0
2
15.8
12.5
10.0
0
04-32
5
30
35
8.0
6.5
DC