The number of start attempts is specified using parameter P1211. The number is internally decreased
after each unsuccessful attempt. After all attempts have been made (as specified in parameter
P1211), automatic restart is cancelled with message F0035. After a successful start attempt, the
counter is again reset to the initial value.
NOTE
The "Flying restart" function (refer to Section 5.9.1) must be additionally activated if,
for an automatic restart, the drive inverter is to be connected to a motor which may
already be spinning.
DANGER
For longer line supply failures (blackouts) and when the automatic restart function is
activated, over a longer period of time it may be assumed that MICROMASTER is
powered-down. However, when the line supply returns, motors can automatically start
to run again without any operator intervention.
If the operating range of the motors is entered in this status, this can result in death,
severe injury or material damage.
5.9.3 PID Control
Refer to Operating Instructions for further details or to Technical Support Website (see page 63)
5.9.4 Sensorless Vector Control (SLVC) / Vector Control (VC)
Refer to Operating Instructions for further details on using Vector Control or Sensorless Vector Control
or to Technical Support Website (see page 67 for contact details)
MICROMASTER 440
6SE6400-5GA00-0BP0
ON always active
Fault F0003 for
Blackout
Brownout
+
restart
Fault acknowl.
+
+
restart
restart
Fault acknowl.
+
+
restart
restart
+
restart
Fault acknowl.
+
+
restart
restart
Table 5-14
Quick Start Guide
All other faults for
Blackout
Brownout
Fault acknowl.
Fault acknowl.
+
+
restart
restart
Fault acknowl.
+
restart
Fault acknowl.
Fault acknowl.
+
+
restart
restart
Automatic Restarts
Issue 08/03
ON in the
no-voltage state
All faults + F0003
Fault acknowl.
Fault acknowl.
+
restart
Fault acknowl.
+
restart
Fault acknowl.
+
restart
61