Siemens MICROMASTER 440 Quick Start Manual page 42

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 08/03
Externally Supplied Control Voltage
Parameter Settings:
Make these changes
AFTER quick
commissioning: see section
5.5 on page 42
These are the default settings
as shown. No parameter
changes are necessary other
than quick commissioning.
Using Fixed Frequencies
Parameter Settings:
Make these changes
AFTER quick
commissioning: see section
5.5 on page 42
P0003=2 (Extended)
P0703[0]=15 DIN3=FF3
P1000[0]=3 (Fixed Frequency)
P1003[0]=FF3
P1004[0]=FF4
42
DIP SW 1
DIP SW 2
(Analog Input 1)
(Analog Input 2)
ON (UP) = 0 to 20mA
ON (UP) = 0 to 20mA
OFF = 0 to 10V
OFF = 0 to 10V
It is necessary for the 0V from the
external system to be connected
to the 0V on the drive to complete
the circuit.
DIP SW 1
DIP SW 2
(Analog Input 1)
(Analog Input 2)
ON (UP) = 0 to 20mA
ON (UP) = 0 to 20mA
OFF = 0 to 10V
OFF = 0 to 10V
This example gives you 2 fixed
frequencies in either direction.
If both Fixed Frequencies are
selected together then the sum of
P1003 and P1004 will be the setpoint.
This may be limited by FMAX/FMIN
Quick Start Guide
RL1
RL1
RL1
NC
NO
COM
A
A
OUT1
OUT1
PTC
PTC
DIN
+
-
A
B
5
AIN1
AIN1
DIN
10V
0V
+
-
1
0-10V Analog Signal
Ext. System 0V
RL1
RL1
RL1
NC
NO
COM
A
A
PTC
PTC
DIN
OUT1
OUT1
A
B
5
+
-
AIN1
AIN1
DIN
10V
0V
+
-
1
RL2
RL2
RL3
RL3
RL3
NO
COM
NC
NO
COM
A
A
DIN
OUT2
OUT2
Iso
P
N
6
+
-
0V
+
-
DIN
DIN
DIN
Iso
AIN2
AIN2
2
3
4
24V
+
-
Ext. System 0V
24V DC External Signal
RL2
RL2
RL3
RL3
RL3
NO
COM
NC
NO
COM
A
A
DIN
OUT2
OUT2
Iso
P
N
6
0V
+
-
+
-
DIN
DIN
DIN
Iso
AIN2
AIN2
2
3
4
24V
+
-
MICROMASTER 440
6SE6400-5GA00-0BP0